ViiFire Servery
Overview
Specification
Examples

 

 

 

FAQS

Q) Can the Servery fire curtain be used in place of a standard fire shutter?

A) Yes - the Servery fire curtain is fully tested for fire resistance in accordance

with BS476-22.8:1987, and has been tested to over 50,000 cycles giving a

longer life span than standard fire shutters. It will not however offer the same

degree of security.

Q) Can the Servery fire barrier be used for regular operations on a daily basis?

A) Yes - The Servery unit is tested to over 50,000 cycles.

Q) On which side of the unit is the motor mounted and what side must the

controls be positioned?

A) The motor is mounted on the left - the controls can be positioned on either

side. It is advisable to position the controls in an accessible position, as low as

possible out of any potential heat build-up.

Q) Is the Servery covered by warranty?

A) The Servery fire curtain is covered by a standard 12 month (return to factory)

warranty. Additional comprehensive 12 and 24 month on site cover is available

(see price list) - contact our Maintenance Department.

Q) What maintenance does the Servery fire barrier require?A) it is a legal requirement to regularly maintain all fire rated equipment. As the

Servery fire barrier is part of a life safety system and is connected to a fire

alarm system there is an obligation under the Regulatory Reform (Fire Safety)

Order 2005 to ensure testing is performed in accordance with BS5588-12.

For details of our service and maintenance options contact our Maintenance

Department.

Q) Will my insurance cover be affected if I do not have my fire containment

equipment regularly serviced by qualified engineers?

A) Yes.

Q) How do I know when I need to replace the batteries and how long do they last?

A) The standard manufacturers’ warranty for batteries is 12 months, however they

can last much longer. Batteries should be regularly checked on maintenance

visits. Unlike traditional fire shutters, the Servery will default to its fire

operational position in the event of battery failure. For further details please

contact our Maintenance Department.

Q) What happens if my Servery fire curtain fails to close to its fire operation

position because an obstruction was present?

A) Call our Maintenance Department immediately for further assistance.The

Servery is a life safety product and failure to do so could make you liable for

prosecution under the Regulatory Reform (Fire Safety) Order 2005. (N.B.The

side channels and the opening should be kept clear at all times - failure to do

so will be a breach of RRO 2005)

Q) When testing my fire curtain and I turn the key-switch back to AUTO from

test, why does the curtain not always retract immediately?

A) There is a minimum delay of 20 seconds that is activated the instant an alarm

signal is received, or the key-switch is operated.This is a safety feature to

protect the motor from abuse, and does not apply to an alarm signal from the

heat or smoke detector (if fitted).

Q) My heat (or smoke) detector was activated and the curtain descended. After

checking that all was clear I pressed the reset detector button and the curtain

did not retract for 5 seconds.Why was that?

A) The control unit contains a built-in safety mechanism, so it generates a 5

second delay to allow the detector to be re-tested. If the detector is clear then

the curtain will retract, if not, the curtain will remain down.

Q) Can I mount the side guides inside a reveal as well as on the face of

an aperture?

A) The Servery is designed to be face-fixed to an aperture. We can

offer alternative models if required - please contact our Technical

Department for further advise.

Q) Can I install the Servery to any type of structure

A) The Servery is supplied with suitable fixings for suitably fire-rated drylined

wall structures. Alternative fixings will be required if fixing to other

surfaces such as masonry, brickwork or reinforced concrete. For further

advice contact our Technical Department.

Q) What happens if I have a mains power cut?

A) Provided the unit is correctly installed following the fitting and

installation instructions, the Servery Standard model will stay retracted

until there is an alarm, or the power is restored. The Servery Plus

model will remain retracted for 30 minutes and then descend under

Gravity Failsafe - or immediately following an alarm signal.

Q) Is the Servery fire curtain easy to connect - what do I need to

provide?

A) The Servery fire curtain unit is fully ‘Plug and Play’. All cables are

provided with snap connectors and power is via a standard factoryfitted

230Vac 13A plug which must be connected to a dedicated supply.

Q) Can you supply a unit over 3.0M wide?

A) The standard product range offers sizes up to 3.0M, (see size chart)

but we will be pleased to quote for special sizes on request.

Q) Do you provide an installation service?

A) Yes - Installation can be provided at additional cost, please contact our

Technical Dept. for details.

Q) Can the unit be boxed in to blend in with my existing decor?

A) Yes - providing any exterior surround should not impair the normal

function of the Severy fire curtain. Any custom made surround should

be suitably fire rated - equivalent to the compartment and the

product. For further details you should seek assistance from your local

Building Surveyor at your local Building Control Division.

Consideration should also be made to access requirements for future

maintenance.

Q) Can the Servery fire curtain be used in a domestic or residential

environment?

A) Yes - the Servery fire curtain is a compact, lightweight and easy-to-fit

unit, ideal for use in the home. Remember that all buildings outside of

dwelling houses will be under the Regulatory Reform (Fire Safety)

Order 2005. It would be advisable to check with your local Building

Control Office.

Q) Can I have my Servery unit in any colour?

A) The standard finish is RAL white - other colours are available at

additional cost (including stainless steel).

Q) How long must I wait for my Servery fire barrier after placing an order?

A) Our standard delivery period is 21 days from receipt of confirmed

order and payment. A longer delivery period will be anticipated for

those units requiring customisation or non-standard finished.

 

Click to download Servery brochure.pdf

 

 

 

 

Specification

 Fire shutter tested for 2hr Fire Resistance to BS476 Part 22.8

 Smoke curtain tested to BS7346 Part 3

 Total power failure Gravity Fail Safe with controlled descent

 Optional smoke or heat detectors

 Simple 13amp Ôplug and playÕ wiring

 Mains power failure warning buzzer

 Stainless steel reinforced fabric with heat reflective coating

 All steel construction - complete with sill plate

 Hygienic, easy wipe surfaces and slim side channels

 Designed to stay in the open position until needed

 Can be used for routine closure of serving area if required

 Long operating life - servery unit tested for over 50,000 cycles

 (C3 Classification BS EN14600)

 

 

 

 

 

 

 

 

 

 

 

 

 